Rep Login (817) 509-2300 info@pottorff.com
blue background, a set of control and backdraft dampers standing out
white paper
Pottorff > Ceiling Radiation Dampers > Ceiling Radiation Dampers > Wood Truss Systems > CFD-521-NP

Model CFD-521-NP

1 Hour - Ceiling Radiation Damper
Field Installed Insulated Duct Board Outlet Box

The CFD-521-NP ceiling radiation damper employs butterfly style blades for point-of-origin control of radiant heat in HVAC systems. The CFD-521-NP is installed horizontally in the ceiling membrane of combustible floor-ceiling or roof-ceiling assemblies with fire resistance ratings up to and including 1 hour. The CFD-521-NP must have a field assembled insulated duct board outlet box installed on it.

CFD-521-NP Field Installed Insulated Duct Board Outlet Box

Standard Construction

Frame: 22 ga. (0.85) galvanized steel.

Blades: 22 ga. (0.85) galvanized steel - butterfly. Insulated with ceramic refractory material for dampers > 114 in2 (735 cm2)

Transition: None (field adaptation required).

Plaster Ground: 5/8" (16) deep x 1" (25) wide.

Closure Device: Fusible Link.

Fire Closure Temperature: 165oF (75oC).

Minimum Size: 4" x 6" (102 x 152)

Maximum Size:
Square: 16" x 16" (406 x 406)
Rectangular: 24" (610) W or 20" (508) H with a maximum area of 256 in2 (1652 cm2).

Ratings

UL 555C Fire Resistance Rating: 1 hour for installation in floor designs L-521, L-528, L-546, L-558, L-562, L-574, L-576, P-581, P-583, L-585, M-509, M-540 and in roof/ceiling designs P-522, P-533, P-538, P-545, P-547 and P-580).

UL 555C Listing: R14603

CSFM Listing: 3226-0368:104

Warnock Hersey Listing #: WHI-495-PSH-0177, -0178

Meets NFPA Standards: 90A and 101

Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC

Click to view or check box to add to cart