1 Hour - Ceiling Radiation Damper
Field Installed Insulated Duct Board Outlet Box
The CFD-521-NP ceiling radiation damper employs butterfly style blades for point-of-origin control of radiant heat in HVAC systems. The CFD-521-NP is installed horizontally in the ceiling membrane of combustible floor-ceiling or roof-ceiling assemblies with fire resistance ratings up to and including 1 hour. The CFD-521-NP must have a field assembled insulated duct board outlet box installed on it.
Frame: 22 ga. (0.85) galvanized steel.
Blades: 22 ga. (0.85) galvanized steel - butterfly. Insulated with ceramic refractory material for dampers > 114 in2 (735 cm2)
Transition: None (field adaptation required).
Plaster Ground: 5/8" (16) deep x 1" (25) wide.
Closure Device: Fusible Link.
Fire Closure Temperature: 165oF (75oC).
Minimum Size: 4" x 6" (102 x 152)
Maximum Size:
Square: 16" x 16" (406 x 406)
Rectangular: 24" (610) W or 20" (508) H with a maximum area of 256 in2 (1652 cm2).
UL 555C Fire Resistance Rating: 1 hour for installation in floor designs L-521, L-528, L-546, L-558, L-562, L-574, L-576, P-581, P-583, L-585, M-509, M-540 and in roof/ceiling designs P-522, P-533, P-538, P-545, P-547 and P-580).
UL 555C Listing: R14603
CSFM Listing: 3226-0368:104
Warnock Hersey Listing #: WHI-495-PSH-0177, -0178
Meets NFPA Standards: 90A and 101
Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC